Whalen Heat Pumps Performance Data

Apartments / Dormitories  |  Hotels | Assisted LivingReplacement Prices | Whalen

Series VI Water Source
Heat Pump & Air Conditioner
Item
1
2
3
4
5
6
Model
VI-A-301
VI-A-401
VI-A-601
VI-A-801
VI-A-1000
VI-A-1200
DB/WB
80/67
80/67
80/67
80/67
80/67
80/67
CFM
340
414
630
827
1002
1200
Fluid
Water
Water
Water
Water
Water
Water
EWT
85
85
85
85
85
85
LWT
95
95
95
95
95
95
GPM
2.32
3.22
4.89
6.30
7.86
9.22
HEAD
10.20
16.80
15.10
25.00
34.00
26.00
Total Cooling Btu/h
8900
12300
18900
24200
30000
34500
Sensible Cool Btu/h
6502
9135
14678
18468
22616
26309
Watts
788
1108
1629
2142
2730
3400
Heat of Rejection
11589
16083
24462
31511
39320
46108
EAT-Heating
70
70
70
70
70
70
EWT
70
70
70
70
70
70
LWT
61.85
62.48
62.27
62.54
64.10
63.55
Heating Btu/h
12501
16002
24999
31099
32498
41000
Watts
893
1143
1787
2222
2734
3305
Heat of Absorption
9453
12099
18901
23514
23167
29720